Weintek cMT3000 HMI Web CGI

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v3 9.8
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Weintek
  • Equipment: cMT3000 CMI Web CGI
  • Vulnerabilities: Stack-based Buffer Overflow, OS Command Injection

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could allow an attacker to hijack control flow and bypass login authentication or execute arbitrary commands.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following Weintek products are affected:

  • cMT-FHD: OS version 20210210 or prior.
  • cMT-HDM: OS version 20210204 or prior.
  • cMT3071: OS version 20210218 or prior.
  • cMT3072: OS version 20210218 or prior.
  • cMT3103: OS version 20210218 or prior.
  • cMT3090: OS version 20210218 or prior.
  • cMT3151: OS version 20210218 or prior.

3.2 Vulnerability Overview

3.2.1 STACK-BASED BUFFER OVERFLOW CWE-121

In Weintek’s cMT3000 HMI Web CGI device, the cgi-bin command_wb.cgi contains a stack-based buffer overflow, which could allow an anonymous attacker to hijack control flow and bypass login authentication.

CVE-2023-38584 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.2.2 IMPROPER NEUTRALIZATION OF SPECIAL ELEMENTS USED IN AN OS COMMAND (‘OS COMMAND INJECTION’) CWE-78

In Weintek’s cMT3000 HMI Web CGI device, an anonymous attacker can execute arbitrary commands after login to the device.

CVE-2023-40145 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H).

3.2.3 STACK-BASED BUFFER OVERFLOW CWE-121

In Weintek’s cMT3000 HMI Web CGI device, the cgi-bin codesys.cgi contains a stack-based buffer overflow, which could allow an anonymous attacker to hijack control flow and bypass login authentication.

CVE-2023-43492 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Taiwan

3.4 RESEARCHER

Hank Chen (PSIRT and Threat Research of TXOne Networks) reported these vulnerabilities to CISA.

4. MITIGATIONS

Weintek recommends users follow their Upgrade Instructions to update the following products to the latest versions:

  • cMT-FHD: OS version 20210211
  • cMT-HDM: OS version 20210205
  • cMT3071: OS version 20210219
  • cMT3072: OS version 20210219
  • cMT3103: OS version 20210219
  • cMT3090: OS version 20210219
  • cMT3151: OS version 20210219

For additional information, refer to Weintek’s security bulletin.

CISA recommends users take defensive measures to minimize the risk of exploitation of this these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time.

5. UPDATE HISTORY

  • October 12, 2023: Initial Publication

Siemens CPCI85 Firmware of SICAM A8000 Devices

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global).

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v3 9.8
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Siemens
  • Equipment: CP-8050, CP-8031
  • Vulnerability: Use of Hard-coded Credentials

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an attacker with knowledge of the corresponding credential to login to the device via SSH.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following products of Siemens, are affected if activated with debug support:

  • CP-8031 MASTER MODULE (6MF2803-1AA00): All versions prior to CPCI85 V05.11
  • CP-8050 MASTER MODULE (6MF2805-0AA00): All versions prior to CPCI85 V05.11

3.2 Vulnerability Overview

3.2.1 USE OF HARD-CODED CREDENTIALS CWE-798

The affected devices contain a hard-coded ID in the SSH authorized_keys configuration file. An attacker with knowledge of the corresponding private key could login to the device via SSH. Only devices with activated debug support are affected.

CVE-2023-36380 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Steffen Robertz, Gerhard Hechenberger, Stefan Viehböck, Christian Hager, and Gorazd Jank from SEC Consult Vulnerability Lab reported the vulnerability on behalf of Netz Niederösterreich GmbH, EVN Gruppe.

4. MITIGATIONS

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

  • CP-8050 MASTER MODULE (6MF2805-0AA00): Update to CPCI85 V05.11 or later version.
  • CP-8031 MASTER MODULE (6MF2803-1AA00): Update to CPCI85 V05.11 or later version.

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage.

For more information see the associated Siemens security advisory SSA-134651 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs). Recognize VPNs may have vulnerabilities, should be updated to the most recent version available, and are only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • October 12, 2023: Initial Publication

CISA Adds Five Known Vulnerabilities to Catalog

CISA has added five new vulnerabilities to its Known Exploited Vulnerabilities Catalog, based on evidence of active exploitation:

  • CVE-2023-21608 Adobe Acrobat and Reader Use-After-Free Vulnerability
  • CVE-2023-20109 Cisco IOS and IOS XE Group Encrypted Transport VPN Out-of-Bounds Write Vulnerability
  • CVE-2023-41763 Microsoft Skype for Business Privilege Escalation Vulnerability
  • CVE-2023-36563 Microsoft WordPad Information Disclosure Vulnerability
  • CVE-2023-44487 HTTP/2 Rapid Reset Attack Vulnerability

These types of vulnerabilities are frequent attack vectors for malicious cyber actors and pose significant risks to the federal enterprise. Note: To view other newly added vulnerabilities in the catalog, click on the arrow in the “Date Added to Catalog” column—which will sort by descending dates.

Binding Operational Directive (BOD) 22-01: Reducing the Significant Risk of Known Exploited Vulnerabilities established the Known Exploited Vulnerabilities Catalog as a living list of known Common Vulnerabilities and Exposures (CVEs) that carry significant risk to the federal enterprise. BOD 22-01 requires Federal Civilian Executive Branch (FCEB) agencies to remediate identified vulnerabilities by the due date to protect FCEB networks against active threats. See the BOD 22-01 Fact Sheet for more information.

Although BOD 22-01 only applies to FCEB agencies, CISA strongly urges all organizations to reduce their exposure to cyberattacks by prioritizing timely remediation of Catalog vulnerabilities as part of their vulnerability management practice. CISA will continue to add vulnerabilities to the catalog that meet the specified criteria.

Qognify NiceVision

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v3 10.0
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Qognify
  • Equipment: NiceVision
  • Vulnerability: Use of Hard-coded Credentials

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an attacker to retrieve sensitive information about the cameras managed by the platform and its users.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of Qoginfy NiceVision, an IP-video surveillance system, are affected:

  • NiceVision: v3.1 and prior

3.2 Vulnerability Overview

3.2.1 USE OF HARD-CODED CREDENTIALS CWE-798

Qognify NiceVision versions 3.1 and prior are vulnerable to exposing sensitive information using hard-coded credentials. With these credentials an attacker can retrieve information about the cameras, user information, and modify database records.

CVE-2023-2306 has been assigned to this vulnerability. A CVSS v3 base score of 10.0 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Commercial Facilities
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: United States

3.4 RESEARCHER

Roni Gavrilov of OTORIO reported this vulnerability to CISA.

4. MITIGATIONS

Qognify has released NiceVision v3.2 UP2 HF2. The latest release is available to customers who have an active SMA (Service Maintenance Agreement) with Qognify.

For more information contact Qognify.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • October 05, 2023: Initial Publication

Atlassian Releases Security Advisory for Confluence Data Center and Server

Atlassian released a security advisory to address a vulnerability affecting Confluence Data Center and Confluence Server. A remote cyber threat actor could exploit this vulnerability to take control of an affected system.

CISA encourages users and administrators to review the following advisory and apply the necessary updates: CVE-2023-22515 – Privilege Escalation Vulnerability in Confluence Data Center and Server.

CISA Releases Three Industrial Control Systems Advisories

CISA released three Industrial Control Systems (ICS) advisories on October 5, 2023. These advisories provide timely information about current security issues, vulnerabilities, and exploits surrounding ICS.

CISA encourages users and administrators to review the newly released ICS advisories for technical details and mitigations.