Softing edgeConnector

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v3 7.2
  • ATTENTION: Low attack complexity
  • Vendor: Softing
  • Equipment: edgeConnector
  • Vulnerabilities: Cleartext Transmission of Sensitive Information, Path Traversal

2. RISK EVALUATION

Successful exploitation of these vulnerabilities could create conditions that may allow remote code execution.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of Softing edgeConnector are affected:

  • Softing edgeConnector: Version 3.60
  • Softing edgeAggregator: Version 3.60

3.2 Vulnerability Overview

3.2.1 Improper Limitation of a Pathname to a Restricted Directory (‘Path Traversal’) CWE-22

The affected product is vulnerable to an absolute path traversal vulnerability, which may allow an attacker with admin privileges to write to a file or overwrite a file in the filesystem.

CVE-2023-38126 has been assigned to this vulnerability. A CVSS v3.1 base score of 7.2 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H).

3.2.2 CLEARTEXT TRANSMISSION OF SENSITIVE INFORMATION CWE-319

The affected product is vulnerable to a cleartext transmission of sensitive information vulnerability, which may allow an attacker to capture packets to craft their own requests.

CVE-2024-0860 has been assigned to this vulnerability. A CVSS v3.1 base score of 8.0 has been calculated; the CVSS vector string is (AV:A/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Pan ZhenPeng (@Peterpan0927) and Li JianTao (@CurseRed) of STAR Labs SG Pte. Ltd. (@starlabs_sg) working with Trend Micro Zero Day Initiative reported these vulnerabilities to CISA. Claroty Team82 working with Trend Micro Zero Day Initiative reported these vulnerabilities to CISA

4. MITIGATIONS

Update Softing edgeConnector and edgeAggregator to v3.70 or greater

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting these vulnerabilities has been reported to CISA at this time. These vulnerabilities are not exploitable remotely.

5. UPDATE HISTORY

  • March 14, 2024: Initial Publication

Siemens Siveillance Control

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global). 

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 6.8
  • ATTENTION: Low Attack Complexity
  • Vendor: Siemens
  • Equipment: Siveillance Control
  • Vulnerability: Incorrect Authorization

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow a local attacker to gain write privileges for objects where they only have read privileges.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following products of Siemens, are affected:

  • Siveillance Control: Versions V2.8 and after until V3.1.1

3.2 Vulnerability Overview

3.2.1 INCORRECT AUTHORIZATION CWE-863

The affected product does not properly check the list of access groups that are assigned to an individual user. This could enable a locally logged on user to gain write privileges for objects where they only have read privileges.

CVE-2023-45793 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been assigned; the CVSS vector string is (CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:N/I:H/A:N).

A CVSS v4 score has been calculated for CVE-2023-45793. A base score of 6.8 has been calculated; the CVSS vector string is (CVSS:4.0/AV:L/AC:L/AT:N/PR:L/UI:N/VC:N/VI:H/VA:N/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Energy
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Siemens reported this vulnerability to CISA.

4. MITIGATIONS

Siemens has released a new version for Siveillance Control and recommends users update to the latest version:

  • Update to V3.1.1 or later version
  • Restrict access to the machine where the Siveillance Control frontend is installed

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage.

For more information see the associated Siemens security advisory SSA-145196 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. This vulnerability is not exploitable remotely.

5. UPDATE HISTORY

  • March 14, 2024: Initial Publication

Siemens SINEMA Remote Connect Client

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global). 

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 6.1
  • ATTENTION: Exploitable remotely/low attack complexity
  • Vendor: Siemens
  • Equipment: SINEMA Remote Connect Client
  • Vulnerability: Insertion of Sensitive Information into Externally-Accessible File or Directory

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow an attacker to access sensitive information.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of Siemens SINEMA Remote Connect Client, a remote management platform, are affected:

  • SINEMA Remote Connect Client: All versions prior to V3.1 SP1

3.2 Vulnerability Overview

3.2.1 INSERTION OF SENSITIVE INFORMATION INTO EXTERNALLY-ACCESSIBLE FILE OR DIRECTORY CWE-538

The product places sensitive information into files or directories that are accessible to actors who are allowed to have access to the files, but not to the sensitive information. This information is also available via the web interface of the product.

CVE-2024-22045 has been assigned to this vulnerability. A CVSS v3 base score of 7.6 has been calculated; the CVSS vector string is (CVSS:3.1/AV:N/AC:L/PR:L/UI:R/S:C/C:H/I:L/A:N).

A CVSS v4 score has also been calculated for CVE-2024-22045. A base score of 6.1 has been calculated; the CVSS vector string is (CVSS4.0/AV:N/AC:L/AT:N/PR:H/UI:P/VC:N/VI:N/VA:N/SC:H/SI:L/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing, Commercial Facilities, Energy, Food and Agriculture, Healthcare and Public Health, Transportation Systems, Water and Wastewater Systems
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Siemens reported this vulnerability to CISA.

4. MITIGATIONS

Siemens has released updates for the affected products and recommends to update to the latest versions:

  • Update to V3.1 SP1 or later version.
  • In order to fully mitigate the issue, administrators are advised to backup and clear the log files and to change the VPN credentials.

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage.

For more information see the associated Siemens security advisory SSA-653855 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of this vulnerability. CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

CISA also recommends users take the following measures to protect themselves from social engineering attacks:

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time.

5. UPDATE HISTORY

  • March 14, 2024: Initial Publication

Siemens SENTRON 7KM PAC3x20

As of January 10, 2023, CISA will no longer be updating ICS security advisories for Siemens product vulnerabilities beyond the initial advisory. For the most up-to-date information on vulnerabilities in this advisory, please see Siemens’ ProductCERT Security Advisories (CERT Services | Services | Siemens Global). 

View CSAF

1. EXECUTIVE SUMMARY

  • CVSS v4 5.1
  • ATTENTION: Low attack complexity
  • Vendor: Siemens
  • Equipment: SENTRON 7KM PAC3120, SENTRON 7KM PAC3220
  • Vulnerability: Improper Access Control

2. RISK EVALUATION

Successful exploitation of this vulnerability could allow attacker to read out the data from the internal flash of affected device.

3. TECHNICAL DETAILS

3.1 AFFECTED PRODUCTS

The following versions of Siemens SENTRON 7KM PAC3120 and PAC3220, power measuring devices, are affected:

  • SENTRON 7KM PAC3120 AC/DC (7KM3120-0BA01-1DA0): Versions V3.2.3 and after but before V3.3.0 only when manufactured between LQN231003… and LQN231215… (with LQNYYMMDD…)
  • SENTRON 7KM PAC3120 DC (7KM3120-1BA01-1EA0): Versions V3.2.3 and after but before V3.3.0 only when manufactured between LQN231003… and
    LQN231215… (with LQNYYMMDD…)
  • SENTRON 7KM PAC3220 AC/DC (7KM3220-0BA01-1DA0): Versions V3.2.3 and after but before V3.3.0 only when manufactured between LQN231003… and LQN231215… (with LQNYYMMDD…)
  • SENTRON 7KM PAC3220 DC (7KM3220-1BA01-1EA0): Versions V3.2.3 and after but before V3.3.0 only when manufactured between LQN231003… and
    LQN231215… (with LQNYYMMDD…)

3.2 Vulnerability Overview

3.2.1 IMPROPER ACCESS CONTROL CWE-284

The read out protection of the internal flash of affected devices was not properly set at the end of the
manufacturing process. An attacker with physical access to the device could read out the data.

CVE-2024-21483 has been assigned to this vulnerability. A CVSS v3.1 base score of 4.6 has been calculated; the CVSS vector string is (AV:P/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N).

A CVSS v4 score has been calculated for CVE-2024-21483. A base score of 5.1 has been calculated; the CVSS vector string is (CVSS:4.0/AV:P/AC:L/AT:N/PR:N/UI:N/VC:H/VI:N/VA:N/SC:N/SI:N/SA:N).

3.3 BACKGROUND

  • CRITICAL INFRASTRUCTURE SECTORS: Critical Manufacturing
  • COUNTRIES/AREAS DEPLOYED: Worldwide
  • COMPANY HEADQUARTERS LOCATION: Germany

3.4 RESEARCHER

Siemens reported this vulnerability to CISA.

4. MITIGATIONS

Siemens has identified the following specific workarounds and mitigations users can apply to reduce risk:

  • SENTRON 7KM PAC3120 AC/DC (7KM3120-0BA01-1DA0), SENTRON 7KM PAC3120 DC (7KM3120-1BA01-1EA0), SENTRON 7KM PAC3220 AC/DC (7KM3220-0BA01-1DA0), SENTRON 7KM PAC3220 DC (7KM3220-1BA01-1EA0): Restrict physical access to the device to trusted personnel.
  • SENTRON 7KM PAC3120 AC/DC (7KM3120-0BA01-1DA0), SENTRON 7KM PAC3120 DC (7KM3120-1BA01-1EA0), SENTRON 7KM PAC3220 AC/DC (7KM3220-0BA01-1DA0), SENTRON 7KM PAC3220 DC (7KM3220-1BA01-1EA0): Update to V3.3.0 or later version.

As a general security measure, Siemens recommends protecting network access to devices with appropriate mechanisms. To operate the devices in a protected IT environment, Siemens recommends configuring the environment according to Siemens’ operational guidelines for industrial security and following recommendations in the product manuals.

Additional information on industrial security by Siemens can be found on the Siemens industrial security webpage.

For more information see the associated Siemens security advisory SSA-792319 in HTML and CSAF.

CISA recommends users take defensive measures to minimize the risk of exploitation of these vulnerabilities, such as:

  • Minimize network exposure for all control system devices and/or systems, ensuring they are not accessible from the internet.
  • Locate control system networks and remote devices behind firewalls and isolating them from business networks.
  • When remote access is required, use more secure methods, such as Virtual Private Networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

CISA reminds organizations to perform proper impact analysis and risk assessment prior to deploying defensive measures.

CISA also provides a section for control systems security recommended practices on the ICS webpage on cisa.gov/ics. Several CISA products detailing cyber defense best practices are available for reading and download, including Improving Industrial Control Systems Cybersecurity with Defense-in-Depth Strategies.

CISA encourages organizations to implement recommended cybersecurity strategies for proactive defense of ICS assets.

Additional mitigation guidance and recommended practices are publicly available on the ICS webpage at cisa.gov/ics in the technical information paper, ICS-TIP-12-146-01B–Targeted Cyber Intrusion Detection and Mitigation Strategies.

Organizations observing suspected malicious activity should follow established internal procedures and report findings to CISA for tracking and correlation against other incidents.

No known public exploitation specifically targeting this vulnerability has been reported to CISA at this time. This vulnerability is not exploitable remotely.

5. UPDATE HISTORY

  • March 14, 2024: Initial Publication

Apple Released Security Updates for Multiple Products

Apple released security updates to address vulnerabilities in Safari, macOS, watchOS, tvOS, and visionOS. A cyber threat actor could exploit some of these vulnerabilities to take control of an affected system. 

CISA encourages users and administrators to review the following advisories and apply the necessary updates: